If the careful use of ?energy? as a resource used to be for cost reasons, today addititionally there is increased environmental awareness. All this also becomes mandatory because of legal requirements and the state of the technology. In this posting you can read about how continuous filter monitoring crucially influences the energy efficiency of something and supports you in complying with legal requirements.
Comparison: New filter ? used filter
Whether with air filters in ventilation and air-conditioning systems or oil filters in hydraulic circuits, in both cases, increasing contamination of the filter element causes an increasing pressure drop. In order to keep the flow of the medium (air or oil) constant, the fan or the pump (respectively) must apply more power. The power consumption increases. Filter monitoring signals the increasing pressure drop across a contaminated filter element. Replacing a fouled filter ensures the flow of the medium and therefore prevents the energy consumption of the fan or the pump from increasing.
Legal bases
With the adoption of the Kyoto Protocol in 1997, europe committed itself to reducing CO2 emissions. So that you can reach this climate goal, in 2005 it adopted the EuP (Energy using Products) directive. In 2009 2009, this is renamed the ErP directive (Energy-related Products directive) ? also referred to as the Ecodesign directive.
Pressure gauge with switch contact, model PGS21
High resistance ? high energy consumption
You can easily understand that a contaminated filter element is more resistant to the flow of a medium than a new, clean element. Physically, the pressure in the inlet (filter inlet) increases ? that may be monitored very well utilizing a pressure measuring instrument ? and the flow rate is reduced. Because the required flow is specified, more energy should be introduced to compensate for the restriction in the filter.
Costs of filter change
Energy-related vs. cost-based considerations
From an energetic viewpoint, a lightly soiled filter ought to be replaced immediately. This conflicts with the truth that the exchange itself generates material and labour costs. In addition, the exchange can only just take place in the absence of both pressure and flow, and therefore the machine or the process must be stopped. Based on these considerations, it is also clear an exchange after a fixed period of use, as we are aware of annual services on cars, for instance, isn’t an optimal solution.
Compromise: Filter monitoring
The compromise can be an acceptable degree of contamination ? meaning a specified maximum differential pressure across the filter. Normal limit values for the differential pressure (?P) of a hydraulic filter are between 1 and 5 bar. In ventilation systems, the limit values are between 50 to 5,000 Pa (0.5 to 50 mbar). Monitoring the pressure drop saves on operating costs, since changing out the filters only happens when near reaching the accepted level of contamination of the filter. An additional advantage is that, through continuous monitoring, the filter replacement could be scheduled into the operational process.
Filter monitoring through measuring the pressure drop
In each case, the pressure drop over the filter is measured ? so ?P between the filter inlet and outlet. However, the pressure loss over the filter also increases with the volume flow. The ?P as a indicator of the contamination of the filter may therefore only be assessed in the defined operating state (flow and medium temperature). Filters for liquids can exceed the ?P limit due to brief pressure peaks. Due to inertia, these are no problem for mechanical switches. For sensors, you should provide a short dead time in the electronic evaluation (control).
Special case: Filter monitoring in hydraulic circuits
The return filters in a hydraulic circuit certainly are a special case. As the name suggests, they are in the return line, right before the oil flows back into the tank. There is ambient pressure (atmospheric pressure) in the tank. Which means that ambient pressure is also present at the filter outlet. This simplifies monitoring, since a differential pressure sensor is now able to dominate the measuring task. It has a favourable influence on the costs of filter monitoring. On the main one hand, these pressure sensors are less costly than differential pressure sensors. On the other hand, you save well on needing a pressure line from the filter outlet to the low-pressure connection of the ?P sensor. Temperature measurement of the oil is essential in hydraulic circuits. This enables the high viscosity of the hydraulic oil, that is still cold when starting, to be studied into consideration, thus avoiding false alerts. The hydraulic oil temperature is required to control the oil cooler. It has a significant influence on enough time over that your oil is used.
Calculation of the excessive differential pressure because of the high viscosity of cold oil
The trend in filter monitoring
Pressure sensor A-1200 with IO-Link
From ?preventive maintenance? to ?Industry 4.0? to IIoT cloud solutions ? there exists เกจวัดแรงดันต่ำ for data everywhere. This could be seen clearly in the change from traditional measuring instruments with optical displays to electrical sensors with analogue or digital output signals. When monitoring pressure filters, we are able to see the trend to displace the differential pressure sensor with gauge pressure sensors before and following the filter. Thus giving one both the system pressure and the pressure at the outlet of the filter, which a differential pressure sensor does not offer. The pressure drop, the difference between your two signals, is then calculated in the electronic control, in the edge computer or in the cloud.
Note
In addition to pressure sensors for filter monitoring, the WIKA portfolio covers all relevant measurement parameters which are essential for controlling and regulating the operating states of a machine or system. Further application examples are available on our website in the ?Industries? section.
Also read our article
Safe filter monitoring with differential pressure gauges