Filter monitoring: A crucial component for energy-efficient operation

If the careful use of ?energy? as a resource used to be for cost reasons, today there is also increased environmental awareness. All this also becomes mandatory thanks to legal requirements and hawaii of the technology. On this page you can find out about how continuous filter monitoring crucially influences the power efficiency of something and supports you in complying with legal requirements.
Comparison: New filter ? used filter
Whether with air filters in ventilation and air-conditioning systems or oil filters in hydraulic circuits, in both cases, increasing contamination of the filter element causes an increasing pressure drop. To keep the flow of the medium (air or oil) constant, the fan or the pump (respectively) must apply more power. The energy consumption increases. Filter monitoring signals the increasing pressure drop across a contaminated filter element. Replacing a fouled filter ensures the flow of the medium and therefore prevents the energy usage of the fan or the pump from increasing.
Legal bases
With the adoption of the Kyoto Protocol in 1997, the European Union committed itself to reducing CO2 emissions. So as to reach this climate goal, in 2005 it adopted the EuP (Energy using Products) directive. In ’09 2009, this was renamed the ErP directive (Energy-related Products directive) ? also referred to as the Ecodesign directive.
Pressure gauge with switch contact, model PGS21
High resistance ? high energy consumption
You can easily understand that a contaminated filter element is more resistant to the flow of a medium than a new, clean element. Physically, the pressure in the inlet (filter inlet) increases ? that can be monitored very well using a pressure measuring instrument ? and the flow rate is reduced. Since the required flow is specified, more energy should be introduced to pay for the restriction in the filter.
Costs of filter change
Energy-related vs. cost-based considerations
From an energetic point of view, a lightly soiled filter ought to be replaced immediately. This conflicts with the fact that the exchange itself generates material and labour costs. In addition, the exchange can only take place in the lack of both pressure and flow, and therefore the machine or the procedure must be stopped. Based on these considerations, additionally it is clear an exchange after a fixed period of use, as we are aware of annual services on cars, for example, is not an optimal solution.
Compromise: Filter monitoring
The compromise can be an acceptable degree of contamination ? meaning a specified maximum differential pressure across the filter. Defiance for the differential pressure (?P) of a hydraulic filter are between 1 and 5 bar. In ventilation systems, the limit values are between 50 to 5,000 Pa (0.5 to 50 mbar). Monitoring the pressure drop saves on operating costs, since changing out the filters only happens when close to reaching the accepted degree of contamination of the filter. An additional advantage is that, through continuous monitoring, the filter replacement could be scheduled into the operational process.
Filter monitoring through measuring the pressure drop
In each case, the pressure drop across the filter is measured ? so ?P between your filter inlet and outlet. However, the pressure loss across the filter also increases with the quantity flow. The ?P as a indicator of the contamination of the filter may therefore only be assessed in the defined operating state (flow and medium temperature). Filters for liquids can exceed the ?P limit as a result of brief pressure peaks. Because of inertia, these are no problem for mechanical switches. For sensors, it is advisable to give a short dead time in the electronic evaluation (control).
Special case: Filter monitoring in hydraulic circuits
The return filters in a hydraulic circuit certainly are a special case. As the name suggests, they are in the return line, right before the oil flows back into the tank. There’s ambient pressure (atmospheric pressure) in the tank. Therefore ambient pressure can be present at the filter outlet. This simplifies monitoring, since a differential pressure sensor can now take over the measuring task. It has a favourable effect on the costs of filter monitoring. On the one hand, these pressure sensors are less expensive than differential pressure sensors. Alternatively, you save well on needing a pressure line from the filter outlet to the low-pressure connection of the ?P sensor. Temperature measurement of the oil is vital in hydraulic circuits. This permits the high viscosity of the hydraulic oil, which is still cold when starting, to be studied into consideration, thus avoiding false alerts. The hydraulic oil temperature must control the oil cooler. It includes a significant influence on the time over which the oil is used.
Calculation of the excessive differential pressure due to the high viscosity of cold oil
The trend in filter monitoring
Pressure sensor A-1200 with IO-Link
From ?preventive maintenance? to ?Industry 4.0? to IIoT cloud solutions ? you will find a demand for data everywhere. This can be seen clearly in the differ from traditional measuring instruments with optical displays to electrical sensors with analogue or digital output signals. When monitoring pressure filters, we can see the trend to displace the differential pressure sensor with gauge pressure sensors before and after the filter. This gives one both system pressure and the pressure at the outlet of the filter, which a differential pressure sensor does not offer. The pressure drop, the difference between your two signals, is then calculated in the electronic control, in the edge computer or in the cloud.
Note
Along with pressure sensors for filter monitoring, the WIKA portfolio covers all relevant measurement parameters which are necessary for controlling and regulating the operating states of a machine or system. Further application examples are available on our website in the ?Industries? section.
Also read our article
Safe filter monitoring with differential pressure gauges

Leave a Comment